Compressor control cabinets: what is inside, and where the base build stops

Two ways people get here. Either a screw compressor runs already, mains pressure keeps swinging and start-stop cycles eat its life. Or it arrived without a drive and needs a panel. We list 25 builds, 0.75 to 315 kW, 3×380 V.

One boundary first, the one most often confused. Our cabinet controls the compressor motor: ramps it up, holds the speed, protects it by current. It does not take over the machine's own controller, pressure switch or unloading logic.

Why sizing a compressor drive by kilowatts fails

A compressor is not a fan. A fan starts almost unloaded; here the shaft must break a piston or screw block against receiver back-pressure and static friction in the oil film. Straight off the mains it draws 5 to 7 times rated current, which is why it goes on a drive. The 150 to 180 % breakaway torque does not go away, and the drive has to deliver the matching current inside its own overload curve: 150 % for about 90 s, 180 % for 10 s, 200 % for 3 s. A drive picked by the kilowatt figure misses that curve on a hard start and trips oL2 (Veichi code 15: inverter overload, not motor). The walkthrough with F-codes: sizing a VFD for a compressor by current.

So we size from the motor nameplate current. The base build carries Veichi at its G rating, the constant-torque figure, because that is the load. Breakaway torque in sensorless vector mode is 150 % of rated from 0.25 Hz (AC310) or 0.5 Hz (AC10), short-term overload 200 % for 3 s. AC310 with an encoder gives 200 % from zero speed.

PowerDrive in base buildDrive rated output currentIP54 enclosure, W×H×D mmBuildPrice, UAH
0.75–4 kWVeichi AC103–9.5 A500×600×300, wallCH-COMP-0R75-38030,604 – 35,536
5.5–11 kWVeichi AC1013–25 A600×1000×300, wallCH-COMP-5R5-38044,311 – 51,964
15–22 kWVeichi AC1032–45 A800×1000×300, wallCH-COMP-015-38064,443 – 79,453
30–45 kWVeichi AC31060–90 A800×1200×400, wallCH-COMP-030-380106,281 – 137,225
55–75 kWVeichi AC310110–150 A1000×1200×400, wallCH-COMP-055-380171,068 – 208,639
90–110 kWVeichi AC310180–210 A800×1800×600, floorCH-COMP-090-380253,972 – 281,325
132–160 kWVeichi AC310250–310 A1000×2000×600, floorCH-COMP-132-380417,686 – 518,876
185–220 kWVeichi AC310340–415 A1000×2200×800, floorCH-COMP-185-380566,154 – 692,177
250–315 kWVeichi AC310470–600 A1200×2200×800, floorCH-COMP-250-380815,857 – 862,938

Prices include VAT, 4 October 2026. The column shows a range per group: left smallest, right largest. Each link opens the smallest power in its group; every build has its own card.

Headroom depends on the frame. From 4 kW up it runs 2.7 to 11.1 % over a typical nameplate: a 17 A drive against roughly 15.4 A on a four-pole 7.5 kW motor. Below that it changes: 43 % at 0.75 kW, and none at all at 2.2 kW where drive current equals the motor rating. A screw compressor loading up gradually is fine on the base margin. A piston machine with a hard start wants one step up. Cheaper than one service call.

Direct links

Power already known? 7.5 kW, 15 kW, 22 kW, 55 kW. The ladder filters by mounting: wall to 75 kW, floor from 90 kW.

Self-check: six lines before you order

Answer these, save a day of email.

  1. Nameplate current and winding connection at 380 V written down? We size the frame from those and check the start against the overload curve.
  2. Screw or piston, and is there a start unloading valve? A piston machine without unloading is the hardest case: one step up.
  3. What controls pressure today: a pressure switch, the compressor's own controller, or nothing? The cabinet leaves that logic where it is.
  4. What minimum speed does the compressor maker allow? That comes from the machine documentation, not the drive, and it limits the range.
  5. How many starts per hour now? If it starts twice a shift and runs fully loaded, a soft starter is cheaper.
  6. One motor, or several machines with alternation? Base build: one drive per motor. Anything else is a separate project.

What the base build includes

By content and price the compressor base build equals the ventilation one. So why not take the ventilation one? Because its drive is sized and tuned for an easy start. In the compressor preset the same money buys different sizing: one step up for a piston machine, ramp times against 150 to 180 % breakaway torque, a check that the start fits the overload curve. A ventilation cabinet on a piston compressor will trip oL2. Pressure logic stays with the compressor controller. We do not touch it.

Included: the Veichi drive, a matched input breaker, an IP54 steel cabinet (dimensions above), climate parts per the calculation, ducts, DIN rails, glands, power and signal wiring, start/stop pushbuttons with lamps on the door, assembly and basic drive setup.

Input breaker: to 185 kW Schneider Electric, on larger frames a device of the matching frame size, model recorded in the spec sheet.

Not included: PLC, operator panel, bypass, cascade control, pressure sensor. A motor choke, a bypass, a door keypad and an IP65 outdoor package are options agreed with an engineer; none changes the cart price.

The drive inside, and related categories

The drive is Veichi AC10 to 22 kW, AC310 from 30 kW. Want only the drive? See the VFD catalogue or pump drives. Neighbouring presets: pump control cabinets, with a pressure sensor in the base, and the control cabinets section.

When the base build is the wrong answer

Several compressors with alternation, receiver pressure from a sensor, an alarm log, a supervisory link: that is a PLC cabinet with an operator panel and a controller. We run those as engineering projects: custom industrial automation design.

Scope of work, build time, payment

What we do: assembly, circuit marking, drive parameters for your motor, circuit checks and a test start. Your electrician mounts it with 150 mm clear above and below the drive as Veichi requires, runs the shielded motor cable with a solid 360-degree shield ground and ties it into the machine's own controller. We do not travel to site; support is remote. Design and assembly as a service: services. Finished work: solutions.

Made to order: 7 to 10 working days.

The card price is fixed; the Buy button works as on any product. Delivery across Ukraine. Payment by bank transfer or online.

The assembled cabinet carries a 24-month warranty under the shop's general warranty terms.

Write to a manager, nameplate current to hand.

Frequently Asked Questions

How do I size a compressor control cabinet?

By the motor nameplate current at 380 V, not by kilowatts. Two motors both marked 7.5 kW from different makers draw different current, and the drive protection trips on current. In the base build, from 4 kW up, headroom is 2.7 to 11.1 % over a typical nameplate, which is enough for a screw compressor. For a piston compressor or a vacuum pump take one build step up.

How does a compressor cabinet differ from a fan cabinet?

By content and price the base build is identical: Veichi drive, input breaker (Schneider Electric to 185 kW, above that a device of the matching frame size), IP54 enclosure, climate parts, wiring, assembly and basic setup. The difference is engineering. The 150 to 180 % breakaway torque demands current inside the drive overload curve, so we size from the nameplate current and tune for a hard start.

Does the cabinet hold receiver pressure automatically?

Not in the base build. There is no pressure sensor in the compressor cabinet; it controls the motor through ramp-up, speed and current protection. Pressure and unloading logic stay with the compressor's own controller or pressure switch. If the cabinet itself must hold pressure from a sensor, that is a custom PLC project.

Why does the compressor throw an oL2 fault at start?

On Veichi, oL1 (code 14) is a motor overload, oL2 (code 15) an inverter overload. When oL2 appears at start, the drive is outside its own overload curve. Check parameters first: longer acceleration (F01.22), less torque boost (F04.01), the right V/F curve (F04.00); the manual lists these before replacing the drive. If breakaway torque still falls outside the curve, parameters will not save it and you need one build step up in power. That is why we ask for nameplate current before the order.

Can two compressors run from one cabinet?

Not in the base build: one drive controls one motor. Two or more compressors with alternation, running-hours balancing or cascade control need a controller and an operator panel, neither of which is in the base build. We deliver that as a separate engineering project against a written specification.

Will this cabinet work with a single-phase 220 V compressor?

No. All 25 builds are designed for a 3×380 V supply. A VFD must not drive a single-phase capacitor motor, because the drive cannot control that load properly. The fix sits on the compressor side: replace the motor with a three-phase one. After the swap we size the cabinet from the new motor current.

What is the protection rating and where can the cabinet go?

The base build is IP54 in a painted steel enclosure, intended for a plant room or workshop. Up to and including 75 kW the build is wall-mounted; from 90 kW it is floor-standing. Outdoor, dusty or damp locations get a separate package. On installation leave at least 150 mm of clear space above and below the drive, per Veichi.

How long is the build time and is the price fixed?

Build time is 7 to 10 working days and the card is marked made to order. The card price is fixed and the Buy button works like any other product, so no quote request is needed. Options are not added to the cart: a motor choke, bypass, door keypad and outdoor package are costed by an engineer and invoiced separately. The assembled cabinet carries a 24-month warranty under the shop's general warranty terms.