Skip to content

PLC + VFD + HMI: Building an Automation System

PLC + VFD + HMI: Building an Automation System

PLC + VFD + HMI bundle: how it works

Most industrial automation systems consist of three components: PLC (logic), variable frequency drive (power section), and HMI panel (operator interface). These three devices, connected via Modbus or Ethernet, form a complete control system for motors, pumps, fans — anything with an electric drive.

We assemble such systems weekly. Typical configuration: Siemens S7-1200 or Delta DVP as the brain, Delta VFD or Sinamics for motor control, and an HMI panel for the operator.

System architecture: who does what

ComponentRoleExample
PLCLogic, interlocks, PID, communicationS7-1200, Delta DVP-SA2, FX5U
VFDMotor speed controlDelta VFD-E, Sinamics V20
HMIDisplay, setpoints, alarmsDelta DOP-107, Siemens KTP700

The PLC is the system center. It reads sensors, calculates logic, and sends commands to the VFD. HMI is the operator window.

PLC-VFD communication: Modbus RTU standard

The most common PLC-to-VFD link is Modbus RTU over RS-485. One PLC can poll 5-20 VFDs on a single bus.

  1. Physical connection: RS-485 two-wire line (A+, B-) from PLC to all VFDs
  2. VFD setup: set Modbus address, speed (9600/19200), parity
  3. PLC programming: write frequency to VFD register, read current and status

More on protocols: Modbus RTU and TCP for PLCs.

PLC-HMI communication: Ethernet or RS-232

  • Ethernet (recommended): fast, reliable. Siemens S7-1200 + KTP700 out of the box
  • RS-232: for Delta DVP + DOP standard link
  • RS-485: HMI as Modbus device, slower

Practical example: pump station

Task: control three pumps maintaining 3.5 bar. Equipment:

  • PLC: Delta DVP-SA2
  • VFDs: 3 x Delta VFD-E 2.2 kW
  • HMI: Delta DOP-107WV
  • Pressure sensor: 0-10 bar, 4-20 mA

Logic: PLC reads the pressure sensor, calculates PID, outputs frequency to the first VFD. If one pump cannot keep up — second one starts. Rotation — daily.

Common mistakes

  • Mismatched Modbus speed: check settings on EVERY device
  • Missing terminator: 120 ohm on last RS-485 device
  • Cable too long: issues start after 500 m
  • One COM port for everything: HMI on RS-232, VFDs on RS-485 — different ports

Frequently Asked Questions

How many VFDs can connect to one PLC?

Via Modbus RTU — up to 247 on one RS-485 bus. In practice, stable operation up to 16-20 devices.

Is an HMI panel mandatory?

No, but highly recommended. Without HMI, the operator cannot see parameters or change setpoints without a laptop.

What cable for RS-485?

Shielded twisted pair (STP), 0.5-0.75 mm2 cross-section. Ground shield on one end only.

Can a VFD be controlled without a PLC?

Yes, via built-in keypad or potentiometer. But then there is no automation: PID, interlocks, pump rotation.

How much does a PLC+VFD+HMI system cost?

For one 2.2 kW motor: $800-1,200. For three 5.5 kW pumps: $3,000-5,000.

Summary

PLC + VFD + HMI is the building block of industrial automation. Modbus RTU over RS-485 connects everything simply and reliably.

Select components: Delta PLCs, Siemens PLCs, HMI panels.

Need a variable frequency drive for your motor?

We'll find the right solution by power, voltage and load type

Browse catalog Consultation

Поширені запитання

Via Modbus RTU — up to 247 on one RS-485 bus. In practice, stable operation up to 16-20 devices.