VEICHI Frequency Converter Setup for Fan Operation

VEICHI Frequency Converter Setup for Fan Operation

The use of frequency converters for fans is also a very popular application. This includes smoke exhausters, supply or exhaust ventilation, aspiration, etc. In this article, we will look at the main parameters for this application. Since proper settings are the key to the normal functioning of the mechanism and will extend its service life, let's move on to the parameters of these frequency converters. Interestingly, the parameters for this application will be the same across all three series.

ParameterDescriptionValue
F00.03Reset to factory settingsSet value to 22.
F02.01Number of motor polesValue from the motor nameplate, or 3000 rpm - 2, 1500 rpm - 4, 1000 rpm - 6, etc. 2*(3000/motor rpm)
F02.02Rated motor power, kWValue from the motor nameplate
F02.03Rated motor frequency, HzValue from the motor nameplate
F02.04Rated motor voltage, VValue from the motor nameplate
F02.05Rated motor speed, rpmValue from the motor nameplate
F02.06Rated motor current, AValue from the motor nameplate
F02.07Motor auto-tuning1. Dynamic tuning (with load connected)

2. Static tuning (if disconnecting the load is not possible). After selection, press the run button. r00-r01-r02-r03-frequency 50.00 or an error code will be displayed.
F01.00Control type0. Asynchronous motor, scalar control
F01.01Frequency inverter start method0. Start from panel (Run/Stop buttons)
1. Start from terminals
F01.02Frequency setting channel

0. Frequency set from buttons on the control panel

1. Frequency set by potentiometer on the panel (if available depending on the model)

2. Frequency set from remote potentiometer for series AC310 and AC10

3. Frequency set from remote potentiometer for series AC01

F01.13Minimum frequencySet the minimum motor operating frequency (choose not less than 15Hz or when the effect starts to appear)
F01.21Acceleration time settingSet the motor acceleration time in seconds (usually not less than 15-20 s)
F01.22Deceleration time settingSet the motor deceleration time in seconds (usually not less than 20 s)
F07.06Auto-start after power loss/power restoration

0. Disabled

1. Auto-catch with speed search (recommended)
2. Standard start

F07.07Auto-start delay time after power restorationSet the auto-start delay time after power appears. (recommended 1 second or more)
F07.10Stop mode

0. Smooth stop (according to parameter F01.22)

1. Coast stop (recommended) parameter F01.22 disabled

F04.00U/F curve selection

0 – linear dependency

1 – power 1.1

2 - power 1.2

3 - power 1.3

4 - power 1.4

5 - power 1.5

6 - power 1.6

7 - power 1.7

8 - power 1.8

9 - power 1.9

10 - power 2 (quadratic)

11 – custom by 5 points (parameters F04.10 – F04.19)

Recommendation: either select according to the fan curve if known or adjust so that the current consumption is minimal. This will be the optimal curve.

Here is the set of necessary parameters for starting the fan operation. If you have additional questions or if the mechanism does not operate as you need, you can refer to the frequency converter's user manual or contact our technical support department, which will assist you.