Skip to content
Selection by parameters

Softstart

Soft starters: what a soft starter actually does

A soft starter works with voltage, not frequency. During ramp-up, three-phase thyristors raise stator voltage from about 30% to 100% over 5-20 seconds; the starting current of an induction motor drops from a typical 6-8·In down to 2-4·In. Once the motor reaches nominal speed, the thyristors are either shorted by an internal bypass contactor or work continues through an external bypass, after which the motor runs directly from the 50 Hz mains. This is a hard limit: a soft starter does not regulate speed and does not save energy under steady-state load. If you need to vary the speed or hold it under changing load, use a VFD; if speed is constant but direct-on-line start damages the network or mechanics, use a soft starter.

We stock 475 models from six manufacturers: Danfoss 180 SKU (MCD200 / MCD500), Schneider Electric 136 (Altistart ATS01, ATS22, ATS48, ATS480, ATS130, ATS430, ATS490), ABB 54 (PSR, PSE, PSTX), Motortronics 42 (Synergy, Agility, PFE), Siemens 36 (SIRIUS 3RW30, 3RW40, 3RW44), Veichi SS70 27. 12-month CRM bestsellers: Danfoss MCD500 (top-1, pump groups 200-1600 A), Schneider ATS01 and ATS130 (light motors), Siemens 3RW30 (panel automation).

Brands and series of soft starters we have

SeriesCurrent / powerBypassWhere it fits
Schneider Altistart ATS013-32 A, up to 15 kWnonesmall motors, infrequent starts
Schneider Altistart ATS2217-590 A, up to 400 kWbuilt-inuniversal: pump, compressor, conveyor
Schneider Altistart ATS4817-1200 A, up to 800 kWexternaltorque-controlled ramp and pump stop
Schneider Altistart ATS48017-1200 A, 8-900 kWbuilt-innew generation, ATS48 replacement with internal bypass
Danfoss MCD50021-1600 Abuilt-inpump groups, water utilities, boiler plants
Danfoss MCD20018-200 Amodel-dependentmid-range motors 7.5-110 kW
ABB PSR4-105 Abuilt-incompact panels, OEM
ABB PSE / PSTX18-2160 Abuilt-inheavy industry, adaptive control
Siemens SIRIUS 3RW306-106 Anonepanel automation, base ramp
Siemens SIRIUS 3RW40 / 3RW4412-432 Amodel-dependentmid-range and heavy motors with torque control
Veichi SS7015-1100 A, 5.5-630 kWbuilt-inbudget segment, pump / fan

Series we advise customers against picking just because they are cheaper: ATS01 on a loaded conveyor (no torque control and no bypass, the thermal trip fires on the first heavy start); SIRIUS 3RW30 on a 75 kW motor with frequent starts (IP20 with no bypass, thyristors overheat); SS70 in applications with more than 10 starts per hour (the series has no proper thermal model).

Real failure modes a soft starter solves

Water hammer in a centrifugal pump. When the pump motor stops directly from the mains, the water column behind the check valve keeps moving by inertia, the valve slams shut, pressure spikes by 5-10 bar. Valves break, welds tear, gauges blow out. A soft starter with a pump stop function (Schneider ATS48, ATS480, Danfoss MCD500) lowers the voltage smoothly over 10-30 seconds so the pump speed and the water column slow down together.

Jerk on a loaded conveyor. A loaded conveyor started direct-on-line takes 200-250% instantaneous torque. The belt slips, couplings break, chains snap. A torque-controlled soft starter (Schneider ATS48 TQ-Control, ABB PSTX, Siemens 3RW44) raises torque along a programmed ramp from an initial torque (typically 30-50%) to 100% over 8-15 seconds without peaks.

High-inertia fan or induced-draft motor. Here there is a trade-off. A soft starter can ramp a motor over 30-40 seconds — but a self-cooled motor barely ventilates at low speed. If you set a 60-second ramp "to be gentle", the winding overheats and the protection trips before reaching nominal speed. For motors with high inertia (fans above 75 kW, crushers) calculate the ramp against the PTC thermistor in the motor, or move to a VFD with vector control.

Piston compressor with torque dips. A piston compressor has torque peaks when the piston crosses top dead centre. Direct-on-line ignores it, but a soft starter with low initial torque stalls. So on piston compressors we set initial torque at no less than 60-70% and a short 5-8 s ramp — or pick ATS480 / MCD500 with adaptive control.

Soft starter vs VFD vs direct-on-line — how to choose

A question we get almost every day: why use a soft starter when a VFD exists? There is a separate article on the site, with the short version below:

  • You need to regulate speed or hold it under a varying load: that needs a VFD, a soft starter does not apply.
  • Speed is constant, but direct-on-line damages the network or mechanics (voltage dips, coupling damage, water hammer): use a soft starter. Two to three times cheaper than a VFD of the same rating, no harmonics injected back to the mains, less heat in the panel.
  • Motor up to 4-5 kW, 1-2 starts per hour, soft load: use a contactor + thermal relay. A soft starter here is overkill, payback measured in years.
  • You want energy savings under steady-state load: that is a VFD with PID, not a soft starter. A soft starter only saves on starting losses and equipment wear.

Soft starter thermal limits: AC-53a and AC-53b

All industrial soft starters are rated under IEC 60947-4-2. The nameplate carries a string like "AC-53a: 3.0-15:85-10". The decoding matters for correct sizing:

  • 3.0: starting current multiplier (3·In). The heavier the load, the higher the figure (4-5·In for crushers).
  • 15: start time in seconds. If your installation wants a 30-second ramp, a "15" series no longer fits, so a model rated for 30-60 s is needed.
  • 85: duty cycle as percentage. 85% means 85 s on, 15 s off. For continuous 24/7 service the rating must be 100%.
  • 10: starts per hour.

AC-53b classification (with an internal bypass contactor) uses another format: "AC-53b: 3.0-15:345". The "345" is the cool-down interval after a series of starts. Series with internal bypass (ATS22, ATS480, MCD500, PSR / PSE / PSTX, SS70) move into bypass right after ramp-up, the thyristors do not heat up, and 20-30 starts per hour are feasible. Series without bypass (ATS01, SIRIUS 3RW30) typically tolerate 6-10 starts per hour before the thyristors overheat and the thermal trip fires.

A special case is drainage and sewage pumps that start dozens of times per hour by tank level. A soft starter normally does not fit here — neither the thermal model nor the thyristor lifetime hold up. The right tool is a VFD for pumps with minimum speed and sleep mode.

What to check before buying a soft starter

A baseline checklist we run with every customer before placing the order:

  1. Motor nameplate current (not the starter datasheet). For standard duty take a soft starter at par or +10%; for heavy duty (loaded conveyor, crusher), +30-50%.
  2. AC-53 load category. Not just motor kW, but also start current multiplier, ramp time, starts per hour. The most expensive mistake to make: the unit fits by kW but the power section dies in a month.
  3. Mechanism type. Pump: pump stop required, hence ATS48 / ATS480 / MCD500. Conveyor: torque control (TQ-Control, ABB PSTX). Piston compressor: adjustable initial torque. Fan: plain ramp plus PTC monitoring.
  4. Internal or external bypass. 10+ starts per hour or a compact panel: internal bypass only (ATS22 / ATS480, MCD500, PSR, SS70). External means a separate contactor, extra wiring, panel space.
  5. Interfaces. Modbus RTU is standard on most series except ATS01 / 3RW30. For Profinet / Ethernet/IP look at ATS480, PSTX, 3RW44 with modules.
  6. Service and spare parts. Ask the customer: planned 7+ years of operation? If yes, Schneider / Danfoss / ABB / Siemens have official service in Ukraine, original control boards and thyristor modules. Budget series are replaced as a whole unit.
  7. Documentation. Verify upfront: is the manual available in your language? Schneider, Danfoss, ABB, Siemens: yes; Motortronics and some Veichi series: English only.

Soft starter by application

Soft starter for pumps (water supply, boiler plants, surface-mounted well pumps). We ask the pump type. Horizontal centrifugal — pump stop function required, pick ATS48 (H075N4 - C32N4) or MCD500. Vertical or submersible: calculate the water-column inertia separately, add a 20-40 s ramp. If the pump starts more than 12 times per hour, switch to a VFD, since a soft starter will not last by lifetime.

Soft starter for conveyor, crusher, mill. A loaded conveyor starts heavy: start multiplier 3.5-4·In, ramp duration 10-15 s. Pick ATS48 with TQ-Control, ABB PSTX with adaptive control or 3RW44 with torque control. A crusher starts with an empty chamber, but on material jam a quick stop is needed, so select models with the quick stop function.

Compressors (screw and piston). A screw compressor starts unloaded in under 5 seconds, and almost any soft starter sized for the motor fits. A piston compressor has a pulsing torque; initial torque 60-70% and a short 5-8 s ramp are required. ATS22 / ATS480 or MCD500 work best.

High-inertia fans and induced-draft fans. A fundamental trade-off: a self-cooled motor overheats at low speed, but high inertia wants a long ramp. Above 75 kW, fit a force-cooled motor plus a soft starter with a 20-30 s ramp, or move to a VFD with fan V/f curve.

Selection by application

Warranty and delivery

All soft starters carry an official manufacturer warranty of 12 to 24 months. Kyiv warehouse, Nova Poshta shipping in 1-3 days across Ukraine. Bank-transfer VAT invoicing for FOP and legal entities, card payment or cash-on-delivery for individuals. Free model selection against a technical brief and parameter setup by an engineer with 10+ years of practice.

Frequently Asked Questions

How is Altistart 22 different from ATS48 and the new ATS480?

ATS22 is the universal base Altistart series with internal bypass; it controls voltage during ramp-up and offers a plain stop ramp. ATS48 adds torque control (TQ-Control) and a full pump stop function for centrifugal pumps, but its bypass is external (a separate contactor in the panel). ATS480 is the new generation and effectively replaces ATS48: TQ-Control, pump stop, plus internal bypass and richer comms (Modbus, optional Profinet / Ethernet IP). For a new pump or conveyor project with torque control, pick ATS480; on new builds the ATS48 no longer makes sense.

How many starts per hour can a soft starter handle?

It depends on whether the unit has an internal bypass. Series with bypass (ATS22, ATS480, Danfoss MCD500, ABB PSR / PSE / PSTX, Veichi SS70) typically take 10-30 starts per hour, because the thyristors switch off after ramp-up and stop heating. Series without bypass (Schneider ATS01, Siemens SIRIUS 3RW30) tolerate 6-10 starts per hour. The exact figure is on the nameplate as AC-53a or AC-53b. If you need over 20 starts per hour with heavy torque, a VFD is more economical than paying for a premium soft starter.

Soft starter or VFD for a pump?

Driven by start frequency and the need to vary flow. If the pump runs in on / off mode by a pressure or level sensor, at up to 10-12 starts per hour, and does not need to hold constant pressure — a soft starter with pump stop (Schneider ATS48 / ATS480, Danfoss MCD500) is two to three times cheaper and fully removes water hammer. If the pump needs to hold network pressure, runs with frequent starts (drainage, sewage), or you need energy savings — pick a VFD with PID. A soft starter gives no savings under steady-state load.

Does a soft starter save energy?

Only on starting losses and through reduced mechanical wear. Under steady-state load the motor is fed straight from the mains via bypass, so consumption matches direct-on-line. Some series (Schneider ATS22, ABB PSTX) offer Inside Delta or Energy Saver, lowering voltage on underloaded motors — but real-world savings are 1-3% and only meaningful on motors permanently running below 50% load. If energy saving is the main goal, the right tool is a VFD with PID, not a soft starter.

What is pump stop and why use it?

Pump stop is a smooth pump-motor stopping function where the soft starter lowers voltage over 10-30 seconds so that pump speed and water-column speed in the pipeline decrease in step. Without pump stop the water column behind the check valve keeps moving by inertia, the valve slams shut and pressure spikes by 5-10 bar — that is water hammer, which breaks valves and welds. The function exists on Schneider ATS48, ATS480, ATS490, ATS430, Danfoss MCD500, ABB PSTX. It does not exist on ATS01, ATS22, MCD200, SIRIUS 3RW30 — these series should not be picked for pump applications.

Do I need an external bypass contactor?

It depends on the series and on start frequency. Series without internal bypass (Schneider ATS01, ATS48, Siemens SIRIUS 3RW30) — an external contactor is recommended for more than 6-10 starts per hour or for 24/7 service; otherwise the thyristors overheat from continuous commutation. Series with internal bypass (ATS22, ATS480, Danfoss MCD500, ABB PSR / PSE / PSTX, Veichi SS70) — no separate contactor needed, bypass engages automatically after ramp-up. The AC-53b figure on the nameplate already accounts for the bypass in start time and duty cycle.

Is a soft starter suitable for frequent starts of a drainage pump?

Usually not. Drainage and sewage pumps cycle dozens of times per hour by tank level — that is 30-60 start / stop cycles. No soft starter series will last that duty: thyristors and internal bypass contactors are typically rated for 10-30 starts per hour. The right tool is a pump VFD (Veichi AC10 with sleep mode, INVT GD20 with PID) running continuously at minimum speed and ramping up when the tank fills — there are effectively no real starts at all.