Skip to content

Danfoss FC 51 Fault Codes: Complete Reference

Danfoss FC 51 Fault Codes: Complete Reference

Danfoss VLT Micro Drive FC 51 Fault and Alarm Codes — Reference Guide

The Danfoss VLT Micro Drive FC 51 is one of the most widely used compact variable frequency drives. It is straightforward to install and reliable when properly wired — but when an alarm code appears on the display, many users are left guessing. What does the number mean? Can it be reset manually? Does it need service?

This page is a complete reference for FC 51 alarm and fault codes. It includes a full alarm table, step-by-step diagnostics for the six most common faults, and an explanation of Trip Lock — the situation where the drive cannot be reset without first fixing the underlying problem. The same codes apply to FC51 (no space) and to the Danfoss FC 101 HVAC Drive — both share identical protection architecture.

For a broader overview of fault codes across multiple VFD brands, see our article on VFD error codes for ABB, Danfoss, INVT and Schneider.

FC 51 Alarm and Warning Code Table

The FC 51 uses three response levels: Warning (drive continues running, signals approach to limit), Alarm/Trip (drive stops, requires reset command) and Trip Lock (drive stays blocked until the fault is physically resolved — reset command has no effect).

CodeNameTypeCause
AL 110V supply lowAlarmVoltage at terminal 50 below 10V — overloaded external sensor or short circuit in analog supply circuit
AL 2Live zero errorWarning/AlarmAnalog input signal below minimum threshold (e.g. broken cable with 4-20 mA configuration)
AL 3No motorWarning/AlarmDrive detects no connected motor — broken phase cable or motor disconnected
AL 4Mains phase lossWarning/AlarmLoss of one or more supply phases
AL 5DC link voltage highWarningDC bus voltage exceeds upper warning threshold — not yet a trip, but approaching overvoltage
AL 6DC link voltage lowWarningDC bus voltage below lower warning threshold
AL 7DC overvoltageAlarm/TripOvervoltage in DC circuit — most often caused by too short a deceleration ramp without a brake resistor
AL 8DC undervoltageAlarmInsufficient supply voltage — mains dips or low input voltage
AL 9Inverter overloadedWarning/AlarmInverter overload — sustained current above rated value
AL 10Motor ETR too hotWarning/AlarmElectronic thermal relay protection triggered — motor overheating per calculated thermal model
AL 11Motor thermistor overtempWarning/AlarmMotor thermistor has detected overtemperature
AL 12Torque limit exceededWarning/AlarmTorque limit reached — motor cannot overcome the load
AL 13OvercurrentAlarm/TripCurrent exceeded protection threshold — mechanical jam, rapid acceleration or faulty motor
AL 14Earth faultTrip LockGround fault in motor circuit — must be resolved before reset is possible
AL 15Short circuitTrip LockShort circuit in output circuit or inside the motor
AL 16Short circuit (hardware)Trip LockHardware short circuit detected by power switch protection circuit
AL 17Control word timeoutWarning/AlarmLoss of communication on control bus — control word timeout
AL 22Hoisting mechanical brakeAlarmMechanical brake fault in hoisting application
AL 23Internal fan faultWarning/AlarmInternal cooling fan not rotating or rotating too slowly
AL 24External fan faultWarning/AlarmExternal cooling fan not operating
AL 25Brake resistor short circuitAlarm/TripShort circuit in brake resistor
AL 26Brake resistor power limitWarningBrake resistor has reached its power dissipation limit
AL 27Brake chopper short circuitAlarm/TripShort circuit in brake chopper transistor
AL 28Brake chopper failureAlarm/TripBrake chopper failure — not switching or not releasing
AL 29Drive overtemperatureAlarm/TripHeatsink or power module overtemperature
AL 30Motor phase U missingAlarmPhase U missing at motor output
AL 31Motor phase V missingAlarmPhase V missing at motor output
AL 32Motor phase W missingAlarmPhase W missing at motor output
AL 33Inrush faultAlarm/TripAbnormal inrush current at power-on
AL 34Fieldbus communication faultWarning/AlarmFieldbus communication error (Modbus, Profibus, etc.)
AL 36Mains failureAlarmMains supply lost during operation
AL 38Internal faultAlarm/TripInternal fault — microprocessor or memory error. Requires restart or service
AL 46PTC supply faultAlarmPTC thermistor supply circuit fault
AL 4724V supply lowAlarmInternal 24V supply below acceptable level
AL 60External interlockAlarmExternal interlock triggered — thermostat, pressure switch or other safety signal activated

Most Common FC 51 Faults — Step-by-Step Diagnostics

Based on service calls we handle, six fault codes come up repeatedly — almost always for the same reasons.

AL 7 — DC overvoltage: braking energy has nowhere to go

The fastest way to get AL 7 is to set too short a deceleration ramp with high-inertia load. The drive tries to brake the motor, but the regenerated energy cannot dissipate — DC bus voltage climbs above 800V and the drive trips.

  • Check: parameter 3-42 (Ramp 2 Down Time) — increase deceleration time
  • If fast braking is required: install a brake resistor — it absorbs the surplus energy
  • Check mains voltage: supply voltage above 253V can also trigger AL 7 even without active braking

AL 13 — Overcurrent: diagnosing the real cause

AL 13 is an overcurrent protection trip, but the root cause varies. Mechanical jam, starting under load without proper ramp settings, or simply a motor too large for the drive.

  1. Check the mechanical side — does the motor shaft turn freely by hand?
  2. Check no-load current — if it is already close to rated, the motor is structurally overloaded
  3. Increase acceleration ramp time (parameter 3-41, Ramp 1 Up Time)
  4. Verify motor nameplate data entered correctly in parameters 1-20 through 1-25

AL 29 — Drive overtemperature: almost always a ventilation problem

The FC 51 is a compact drive and its thermal performance depends heavily on proper installation. Overtemperature rarely means a faulty drive — it nearly always means poor airflow.

  • Minimum clearance above and below — 100 mm, between drives in a row — 50 mm
  • Ambient temperature must not exceed +40°C without derating
  • Check the cooling fan — AL 23 often precedes AL 29 by a few hours or days
  • Drives in sealed enclosures without forced ventilation will overheat under sustained load

AL 14 — Earth fault: Trip Lock, must fix before resetting

AL 14 is a Trip Lock fault. Pressing Reset does nothing until you locate and fix the ground fault. This alarm points to damaged insulation in the motor cable or motor windings.

  1. Disconnect the motor cable from drive output terminals U, V, W
  2. Test cable insulation with a megohmmeter: resistance between each conductor and screen/earth must exceed 1 MOhm
  3. Test motor winding insulation separately
  4. If damage is found — replace the cable or arrange motor repair

AL 10 — Motor ETR: calculated thermal protection

ETR (Electronic Thermal Relay) is a software thermal model. It calculates motor heating based on current history. If motor nameplate data in parameter 1-24 (Motor Current) is wrong, ETR may trip even during normal operation.

  • Verify parameter 1-24 matches the motor nameplate current rating
  • Check parameter 1-61 (Motor ETR Setting) — enabled by default, works for most standard motors
  • If the motor is actually hot to the touch — reduce load or improve cooling

AL 2 — Live zero error: broken 4-20 mA signal

When the analog input is set for 4-20 mA and the signal drops below 2 mA, the FC 51 treats this as a broken sensor and raises AL 2. Common causes: wrong wiring, broken cable, or failed sensor.

  • Check sensor wiring to terminals 53/54 and 55 (common)
  • Check parameter 6-16 (Terminal 53 Low Current) — default is 4 mA
  • If the sensor is healthy — test the cable for open circuit or loose connection

Trip Lock Faults — What to Do When the Drive Will Not Reset

Trip Lock means the drive stays blocked regardless of reset commands. Three FC 51 codes are Trip Lock by default: AL 14 (earth fault), AL 15 and AL 16 (short circuits).

Procedure for Trip Lock faults:

  1. Switch off drive power and wait 5 minutes for DC bus to discharge
  2. Disconnect motor cable from output terminals U/V/W
  3. Test insulation with megohmmeter — cable and motor separately
  4. For AL 15/16: also check for foreign objects in motor, verify cable termination integrity
  5. Fix the identified fault
  6. Restore power — if the fault is resolved, the drive should exit Trip Lock automatically

For more on VFD failures and repair procedures, see our guide on frequency converter breakdowns and repairs.

Configuring Fault Responses in FC 51

The FC 51 allows you to customise how the drive responds to specific faults. This is useful when the default behaviour does not fit your application.

Parameter Group 14-xx — Drive Information / Fault Handling

  • 14-10 Mains Failure: action on mains loss — Trip, Coast or Kinetic backup
  • 14-12 Function at Mains Imbalance: response to mains imbalance — Warning or Trip
  • 14-20 Reset Mode: manual or automatic reset (and number of auto-restart attempts)
  • 14-21 Automatic Restart Time: delay before automatic restart (0-600 s)
  • 14-22 Operation Mode: normal operation or service mode

Automatic Restart

Parameter 14-20 supports up to 20 automatic reset attempts with adjustable interval. This is practical for pump and fan applications where brief mains interruptions are common. Do not enable auto-restart for hoisting equipment — uncontrolled restart is a safety hazard.

AL 2 Response (Live zero)

Parameter 6-01 (Live Zero Timeout Function) sets what happens when the analog signal is lost: stop, go to a preset frequency, or hold the last commanded frequency. For pumps, stopping is typical. For ventilation systems, a fixed fallback frequency of 30-40 Hz is common.

For fault code comparisons across other popular drives, see VFD error codes for ABB, Danfoss, INVT and Schneider.

Frequently Asked Questions

What is the difference between Warning and Alarm on the FC 51?

A Warning means the drive continues running but has detected a condition approaching a limit. An Alarm (Trip) means the drive has stopped and requires a reset command or button press. Trip Lock is a separate state where no reset is effective until the physical fault is fixed.

How do I reset a fault on the Danfoss FC 51?

Press the Reset button on the LCP keypad, or apply a Reset signal to the configured digital input (default: terminal 27). You can also reset via parameter 14-20 or via a Modbus command. For Trip Lock faults, power down the drive first, fix the fault, then restore power.

What is AL 38 Internal fault and how do I fix it?

AL 38 indicates a microprocessor or memory fault inside the drive. First try a full power-down for 5-10 minutes. If AL 38 reappears after restart, try a factory reset via parameter 14-22 (Operation Mode → Factory reset). If the fault persists, the drive requires professional service or replacement.

Do these codes apply to the Danfoss FC 101 HVAC Drive?

Yes, largely. The FC 101 shares the same core protection architecture as the FC 51, and most alarm numbers and meanings are identical. However, the FC 101 has additional application-specific codes related to its advanced pump and fan control features that are not present in the FC 51.

How can I prevent AL 7 (DC overvoltage) without a brake resistor?

Increase the deceleration ramp time in parameters 3-42 / 3-82 (Ramp Down Time). For loads with significant inertia, enable the Over-voltage control function (parameter 2-17) — it automatically extends the deceleration ramp when DC bus voltage approaches the trip threshold. This does not replace a brake resistor for demanding applications, but works well for lighter loads.

If your FC 51 has failed or needs replacement, browse our Danfoss frequency converter catalogue. We can source genuine units and compatible alternatives from stock.

Need a variable frequency drive for your motor?

We'll find the right solution by power, voltage and load type

Browse catalog Consultation

Поширені запитання

Trip Lock is a locked fault state where the drive does not respond to any reset command. It is triggered by AL 14 (earth fault), AL 15 and AL 16 (short circuits). To exit Trip Lock, power down the drive, fix the physical fault, then restore power.